Segmented route voltage drop calculator
Estimate Australian voltage drop across a segmented cable route from entered segment lengths, cable data and load current.
Vdrop_total = sum(mVAm_i x I x L_i / 1000); Vdrop_% = Vdrop_total / V x 100; margin_% = target_% - Vdrop_%- Segment mV/A/m values are entered by the user.
- Optional blank segments are treated as unused.
- The page sums segment drops only.
- It does not reproduce controlled cable tables or decide compliance.
| Variable | Meaning | Unit | Use |
|---|---|---|---|
| mVAm_i | Segment cable data | mV/A/m | Entered voltage-drop data for each segment. |
| I | Load current | A | Current flowing through the route. |
| L_i | Segment length | m | Entered one-way length for each segment. |
| Vdrop_total | Total voltage drop | V | Sum of each segment voltage drop. |
| Vdrop_% | Voltage drop percent | % | Total drop divided by the entered voltage basis. |
| target_% | Entered target | % | User-entered project comparison target. |
| margin_% | Target margin | % | Entered target minus calculated voltage-drop percent. |
More
Segmented route voltage drop calculator technical guide
Estimate Australian voltage drop across a segmented cable route from entered segment lengths, cable data and load current.
Use this calculator when a cable run has distinct route segments with different lengths or cable data values. It keeps each segment visible, then adds the voltage drop contributions into one project record.
Field use cases
| Work setting | Real question | Useful action from this page |
|---|---|---|
| Board-to-board route | Which segment contributes most of the total drop? | Enter each length and mV/A/m value separately. |
| Mixed cable data | How much does a cable-size change affect the route total? | Keep each segment source value visible. |
| Long upstream section | Is the long segment dominating the result? | Review the largest segment output first. |
| Design review record | Is the total inside the entered project target? | Compare total percent drop with the entered target. |
| Route revision | Which changed segment should be updated? | Adjust only the affected segment inputs. |
The page is intentionally a segment summation worksheet. For one uniform run, the standard voltage-drop calculator is cleaner.
Data checklist
| Value | Where it normally comes from | Stop if |
|---|---|---|
| Segment length | Drawing, cable schedule or measured route | The entered length is not one-way route length. |
| Segment mV/A/m | Cable data source or project record | The value belongs to another cable or installation basis. |
| Load current | Load calculation or design record | Current differs between segments and the route model has not been reviewed. |
| Voltage basis | Supply or equipment basis | Percent drop is being compared to the wrong voltage. |
| Target percent | Project requirement or design assumption | The target is not documented. |
If segment data is uncertain, keep the result as a draft calculation record.
Method comparison matrix
| Method element | What this calculator does | What remains outside |
|---|---|---|
| Segment drop | Calculates mV/A/m x current x length / 1000. | Selecting the mV/A/m value. |
| Route total | Adds each populated segment drop. | Whether the route split is the right design model. |
| Largest segment | Identifies the highest segment contribution. | Engineering decision on which segment to change. |
| Target margin | Compares total percent with user-entered target. | Final standards or project approval. |
The result is most useful when the worksheet shows enough detail for another reviewer to repeat the segment total.
Worked records
| Situation | Inputs | Result | Record use |
|---|---|---|---|
| Mixed route | 63 A, 400 V, segments 25 m, 18 m and 12 m | 5.647 V total, about 1.41% | Segment one is the largest contributor. |
| Long first segment | 70 A with a 58 m first segment | Long segment review applies | Review route allocation and cable data. |
| Target exceeded | Three longer segments with a 1% target | Outside the entered target | Review segment data and route design. |
The examples show why a segmented route should not be hidden inside one average cable-data value.
Stop points
- Segment lengths are not on the same one-way route basis.
- mV/A/m values are copied from unrelated cable data.
- The route has changing load current between segments and needs a different model.
- The total is above the entered target and no segment review has been done.
- The result is being used as final compliance evidence without project review.
A useful export record includes the route reference, current, voltage, target, each segment length, each mV/A/m value, total voltage drop and largest segment.
Mixed cable route
A route changes cable data after a board, then again through a final equipment section.
- Route reference
- SEG-ROUTE-1
- Load current
- 63 A
- Voltage
- 400 V
- Segments
- 25 m, 18 m, 12 m
- Segment drops3.31 V, 1.64 V, 0.7 V by entered segment.
- Total drop5.65 V across the entered route.
- Percent drop1.41% against the entered voltage basis.
Target margin is 0.59%.
The segmented route is inside the entered target, with segment one contributing the largest drop.
- Each mV/A/m value is entered from the project cable data source.
- The route is summed as three one-way segments.
- This page does not replace the single-run voltage-drop calculator.
Long first segment review
A long upstream segment dominates the total drop and needs separate route review.
- Route reference
- LONG-SEGMENT-1
- Load current
- 70 A
- Voltage
- 400 V
- Segments
- 58 m, 16 m, 0 m
- Segment drops8.93 V, 1.34 V, 0 V by entered segment.
- Total drop10.28 V across the entered route.
- Percent drop2.57% against the entered voltage basis.
Target margin is -0.57%.
The route is close enough to the entered target that the long first segment should be reviewed.
- Blank segment three is treated as 0 m.
- The entered target is a project value.
- Cable-size selection remains outside this worksheet.
Target exceeded route
Three segments are entered for a longer route where the voltage-drop target is tighter.
- Route reference
- SEG-REVIEW-1
- Load current
- 63 A
- Voltage
- 400 V
- Segments
- 50 m, 30 m, 20 m
- Segment drops6.62 V, 2.74 V, 1.16 V by entered segment.
- Total drop10.51 V across the entered route.
- Percent drop2.63% against the entered voltage basis.
Target margin is -1.63%.
The sum is above the entered target, so cable data, route splits and target basis need review.
- All segment data is entered by the user.
- The largest segment is highlighted for review.
- The result is not a final compliance decision.