Voltage drop calculator
Estimate AC voltage drop for a 230/400 V, 50 Hz Australian cable run using entered current or power, route length in metres and project conductor data.
Vd = mV/A/m x I x L / 1000; Vd = F x I x Lkm x (R x PF + X x sin(arccos(PF))); Vdrop% = Vd / Vn x 100; Vreceiving = Vn - Vd; Lmax = target_Vdrop / method_factor- Use 230 V as the default single-phase context and 400 V as the default three-phase line-to-line context.
- The mV/A/m mode uses user-entered project data and does not reproduce cable standard tables.
- The impedance mode uses entered resistance and reactance values in ohm/km.
| Variable | Meaning | Unit | Use |
|---|---|---|---|
| Vd | Voltage drop across the cable run | V | Primary calculated result. |
| I | Load current used in the voltage-drop calculation | A | Entered directly or calculated from kW or kVA. |
| L | One-way route length | m | Length of the cable route being checked. |
| Lkm | One-way route length | km | Route length converted from metres for impedance mode. |
| F | Phase factor | factor | Single-phase or three-phase factor applied by the selected supply arrangement. |
| mV/A/m | Voltage-drop data entered from the project source | mV/A/m | Must match the cable and circuit context being reviewed. |
| R | Conductor resistance entered by the user | ohm/km | Used in impedance mode. |
| X | Conductor reactance entered by the user | ohm/km | Used in impedance mode. |
| PF | Power factor | decimal | Used for kW input and impedance mode. |
| Vn | Nominal supply voltage | V | Used to calculate voltage-drop percentage. |
| Vdrop% | Voltage-drop percentage | % | Voltage drop divided by nominal voltage. |
| Vreceiving | Receiving-end voltage | V | Nominal voltage less calculated voltage drop. |
| Lmax | Maximum one-way route length | m | Inverse length result using the entered project target and same calculation basis. |
More
Voltage drop calculator technical guide
Estimate AC voltage drop for an Australian cable run using entered current or power, route length and project conductor data.
Field use cases
Use this calculator when a cable run already has a load basis, a one-way route length and a project cable data source, and the reviewer needs a transparent AC voltage-drop estimate before moving into cable selection or installation documentation. Typical field uses include checking a proposed final subcircuit, comparing two route options, reviewing a submain allocation, or documenting the voltage-drop basis for a load schedule.
The result is a preliminary engineering estimate. It shows the voltage drop in volts, the percentage of the entered nominal voltage, the estimated receiving-end voltage and the maximum one-way route length implied by the entered target. It does not choose a conductor size, prove current-carrying capacity, decide grouping or derating, select protective devices, or make a final installation decision.
The default Australian supply context is 230 V single phase and 400 V three phase at 50 Hz. Treat those values as starting points for the project basis. For three-phase calculations, use the line-to-line voltage that belongs with the circuit being reviewed.
Data to confirm before checking a run
Confirm the load current before relying on the voltage-drop result. A known equipment or design current is usually stronger than a power conversion. If only kW or kVA is available, keep the conversion basis with the calculation record, including the selected supply arrangement and power factor where it is used.
Confirm the route length as the installed one-way cable path. Include vertical rises, bends, switchboard position, route deviations and termination allowance where they are part of the reviewed route. A straight drawing distance can understate the voltage drop if it omits the actual cable path.
Confirm the cable data source before choosing the method. The entered mV/A/m value or R/X impedance values should describe the same conductor, circuit arrangement, temperature basis, source document and installation context being reviewed. The calculator does not reproduce controlled cable tables, and it cannot correct a cable data value that belongs to a different cable or condition.
| Review item | Confirm before using the result | Stop if |
|---|---|---|
| Load basis | Current source, or kW/kVA conversion basis. | The load is only a rough allowance and no design current is available. |
| Route length | Installed one-way path in metres. | The route is still a drawing shortcut or excludes risers and deviations. |
| Supply context | 230 V single phase or 400 V three phase unless project documents state otherwise. | The entered voltage does not match the circuit arrangement. |
| Cable data source | mV/A/m or R/X values for the selected cable context. | The data source, conductor or installation basis cannot be identified. |
| Project target | The review percentage used for this project stage. | The target is being treated as an automatic authority limit or final decision. |
Method comparison matrix
Choose the method that matches the data available for the run. The method is a source judgement, not a preference for whichever entry is quicker.
| Method or load basis | Best use | Practitioner check |
|---|---|---|
| mV/A/m cable data | Project, manufacturer or licensed cable data already provides a voltage-drop value for the selected context. | Confirm the value matches conductor material, cable size, arrangement and source basis. |
| R/X impedance data | Resistance and reactance are available and the reviewer wants impedance-based arithmetic. | Confirm R, X and power factor describe the same operating basis. |
| Entered current | Nameplate current, design current or another reviewed current value is available. | Keep the current source with the record. |
| kW conversion | Real power is known and power factor is available. | Check that the power factor is suitable for the equipment and review stage. |
| kVA conversion | Apparent power is the available rating. | Confirm whether the kVA value is per item, per phase or total load. |
How to read the result
Read volts, percentage and receiving-end voltage together. The voltage drop in volts is the calculated loss along the entered route. The percentage compares that loss with the entered nominal voltage. The receiving-end voltage shows the nominal voltage less the calculated drop. A percentage without the voltage basis, route length and load current is not enough information for another reviewer to repeat the check.
The maximum length result is an inverse calculation from the entered target using the same assumptions. It is useful for route review, but it is not a statement that the route can be installed without further checks. If current, cable data, power factor, installation basis or project target changes, the maximum length changes as well.
When the calculated percentage is above the entered target, review the route before relying on the result. The response might be a shorter route, different distribution point, revised load assumption, different cable data, larger candidate conductor, or a documented project decision. This calculator does not choose that response.
Worked Australian examples
Single-phase final subcircuit
A 32 A single-phase circuit is reviewed over a 40 m route. The project source gives voltage-drop data of 2.8 mV/A/m for the cable context being checked. The nominal voltage is 230 V and the project target entered for review is 5%.
The calculation is:
2.8 x 32 x 40 / 1000 = 3.58 V
The percentage drop is:
3.58 / 230 x 100 = 1.56%
The result is below the entered target. It can be carried forward as a voltage-drop estimate only with the 2.8 mV/A/m data source, the 32 A current basis and the 40 m route length attached. It does not decide conductor current capacity, grouping, installation method or protective-device suitability.
Three-phase equipment run
A balanced three-phase item is listed as 25 kW. The supply context is 400 V line-to-line, the power factor entered for the calculation is 0.85, and the route length is 60 m. The project data source gives conductor resistance of 1.15 ohm/km and reactance of 0.08 ohm/km.
The calculator first converts 25 kW into current using the three-phase relationship. The current used is about 42.45 A. It then applies the entered resistance and reactance values with the three-phase phase factor and power factor. The resulting voltage drop is about 4.50 V, or about 1.12% of 400 V.
This is an impedance-based estimate. Store it with the entered R, X, PF and length values. If equipment data later gives a different current, or the cable data changes with conductor selection, repeat the calculation.
Long lighting circuit review
A 20 A single-phase lighting circuit is being checked over a 90 m one-way route. The project source gives 4.4 mV/A/m for the cable context being considered, the nominal voltage is 230 V, and the project target entered for this review stage is 3%.
The calculation is:
4.4 x 20 x 90 / 1000 = 7.92 V
The percentage drop is:
7.92 / 230 x 100 = 3.44%
This result is above the entered 3% target. Treat it as a route-review trigger, not as a final defect label. Review why the route is long, whether the length includes real installation allowances, whether the cable data matches the candidate conductor, whether the load current is the right basis, and whether a different route, distribution point or conductor candidate should be considered. The maximum-length result is also useful here because it shows the same assumptions would need a route of about 78.4 m to sit at the entered target.
Minimum export record
Export only after the calculator has a valid result and a traceable run reference. The PDF should capture the calculation result; the project file should retain the cable-data source and any standards, DNSP, manufacturer or design-review basis.
| Record item | Include in or beside the export | Why it matters |
|---|---|---|
| Project reference | Circuit, cable run, switchboard, drawing or schedule reference | Ties the result to a real route |
| Supply and voltage basis | Single-phase or three-phase context and nominal voltage | Makes the percentage result repeatable |
| Load basis | Current, kW/PF or kVA basis used to derive current | Confirms the load current used in the calculation |
| Route length | One-way route length in metres | Confirms the length was not a drawing shortcut |
| Cable data source | mV/A/m value or R/X impedance values and source | Keeps the result tied to the conductor and installation basis |
| Project target | Entered voltage-drop target and source | Separates the review target from an automatic authority decision |
| Result summary | Voltage drop, percent, receiving-end voltage and maximum length | Provides the values needed for the next review step |
| Reviewer | Electrician, engineer, estimator or reviewer name | Makes the exported record traceable to a named reviewer |
Review workflow
- Confirm the load source. Use known current where possible, or record the kW/kVA conversion basis.
- Confirm the route length. Use the installed one-way cable path and note any provisional sections.
- Select the cable data method. Match mV/A/m or R/X values to the project source being reviewed.
- Enter the project target. Use the percentage set for this project stage or design review, not an assumed authority rule.
- Review volts, percent and receiving-end voltage together. Check whether the route needs attention before the result is filed.
- Carry the result into the next task only with the current, length, cable data source, method and target attached.
Boundary with cable size selection, submain allocation and inverter/battery routes
Voltage drop is one check in a wider review. A cable can have an acceptable voltage-drop estimate and still need review against another design requirement. A route can also need voltage-drop attention even when current capacity appears adequate.
| Adjacent task | How this calculator helps | What remains outside this route |
|---|---|---|
| Cable size selection | Compares voltage-drop effect for entered cable data. | Current-carrying capacity, installation method, grouping, derating, protection and final selection. |
| Submain allocation | Supports one part of a total voltage-drop allocation. | Allocation policy across consumer mains, submains and final circuits. |
| Load schedule review | Records the drop for the nominated load basis. | Demand assumptions and whether current is connected, diversified or measured. |
| Inverter AC cable route | General voltage-drop arithmetic can inform a non-solar cable run. | Inverter export voltage-rise treatment and solar-specific assumptions. |
| Battery DC cable route | None for DC battery cable voltage-drop work. | DC polarity, loop length, battery voltage, fault energy and battery manufacturer constraints. |
| Final installation decision | Provides transparent arithmetic for review. | Current Australian standards, DNSP conditions, product instructions, inspection requirements and project documentation. |
The support utilities for percent conversion, maximum route length by target and mV/A/m entry stay inside this route because they depend on the same current, voltage, length and cable data assumptions. They should not be separated into smaller tools without a complete task promise and evidence review.
Australian standards and authority context
Australian electrical installation work must be checked against current standards, local authority or DNSP conditions, product instructions and project documentation. This calculator uses transparent arithmetic. It does not reproduce protected standard tables and does not claim that a result is a final installation decision. Where a standard, connection requirement or project specification sets a voltage-drop requirement, enter that requirement as the project target and keep the source with the calculation record.
AS/NZS cable selection and installation context can involve conductor material, insulation, installation method, ambient temperature, grouping, protective devices and other factors. Those factors are not solved by this page. They may affect the cable data entered into the calculator and may govern whether a cable is suitable for the installation.
Stop points
- Stop if the route length is still a straight-line drawing estimate rather than the installed one-way cable path.
- Stop if the cable data source cannot be matched to the conductor, circuit arrangement and installation basis being reviewed.
- Stop if the load current is a rough assumption and a reviewed design current or equipment current is available elsewhere.
- Stop if the entered voltage does not match the single-phase or three-phase supply context.
- Stop if the percentage result is being used on its own without volts, receiving-end voltage, load current, route length and cable data source.
- Stop if the result is being treated as cable selection, submain allocation acceptance, inverter AC route acceptance, battery DC cable assessment or final installation decision.
- Stop if current standards, DNSP requirements, manufacturer instructions or project documentation set conditions that have not been checked.
A useful calculation record states the run reference, load current, voltage basis, cable data source, project target and result. For example: "Run reference FINAL-CCT-1, 32 A, 230 V single phase, 40 m route, 2.8 mV/A/m project cable data, calculated drop 3.58 V or 1.56%." That record gives another reviewer enough information to understand the basis and repeat the calculation.
Single-phase workshop final subcircuit
A 32 A final subcircuit to workshop equipment is reviewed over a 40 m one-way route using project-entered voltage-drop data of 2.8 mV/A/m.
- Run reference
- FINAL-CCT-1
- Supply arrangement
- Single phase
- Nominal voltage
- 230 V
- Load basis
- 32 A
- One-way route length
- 40 m
- Cable data
- 2.8 mV/A/m
- Project target
- 5%
- Current used32 A entered directly for the cable-run review.
- Cable data applied2.8 mV/A/m is applied across the 40 m one-way route.
- Voltage drop percentage1.56% of the entered nominal voltage.
- Receiving-end voltage226.42 V before any separate design review.
Voltage drop is 1.56% of the entered nominal voltage. Maximum one-way route length at the entered target is approximately 128.3 m.
The voltage-drop estimate is below the entered project target. The result can be carried into the design record only with the cable data source, route measurement and separate cable selection checks.
- 230 V single-phase Australian low-voltage context.
- mV/A/m data is entered from the project cable data source.
- No cable current-carrying capacity, derating or protective-device decision is made.
Three-phase mechanical plant run
A 25 kW balanced three-phase mechanical load is reviewed at 400 V over a 60 m route using entered conductor resistance and reactance values.
- Run reference
- MECH-RUN
- Supply arrangement
- Three phase
- Nominal voltage
- 400 V
- Load basis
- 25 kW
- One-way route length
- 60 m
- Cable data
- 1.15 ohm/km R, 0.08 ohm/km X
- Project target
- 5%
- Current used25 kW at 400 V three phase gives 42.45 A.
- Cable data applied1.15 ohm/km resistance and 0.08 ohm/km reactance are applied at PF 0.85.
- Voltage drop percentage1.12% of the entered nominal voltage.
- Receiving-end voltage395.5 V before any separate design review.
Voltage drop is 1.12% of the entered nominal voltage. Maximum one-way route length at the entered target is approximately 266.8 m.
The result is an impedance-based estimate for the entered three-phase load and route length. It should be checked against the cable data source, motor or equipment data and installation assumptions before being used.
- 400 V line-to-line Australian three-phase context.
- The load is treated as balanced for this worksheet calculation.
- Resistance and reactance values are entered project data, not values selected by the calculator.
Long lighting circuit review
A 20 A single-phase lighting circuit is checked over a 90 m one-way route where the project target for this review stage is 3%.
- Run reference
- LIGHTING-RUN
- Supply arrangement
- Single phase
- Nominal voltage
- 230 V
- Load basis
- 20 A
- One-way route length
- 90 m
- Cable data
- 4.4 mV/A/m
- Project target
- 3%
- Current used20 A entered directly for the cable-run review.
- Cable data applied4.4 mV/A/m is applied across the 90 m one-way route.
- Voltage drop percentage3.44% of the entered nominal voltage.
- Receiving-end voltage222.08 V before any separate design review.
Voltage drop is 3.44% of the entered nominal voltage. Maximum one-way route length at the entered target is approximately 78.4 m.
The entered route is above the project target. The result should trigger review of the route, cable data and load basis before a conductor or distribution change is documented.
- 230 V single-phase Australian low-voltage context.
- The 90 m length is treated as the installed one-way route.
- The 3% target is a project review value entered by the user, not a universal installation limit.