RCD test checker
Compare an Australian RCD or RCBO measured test row with the entered criterion and expected outcome.
Itest = I_dn x m; margin_ms = tmax_ms - tmeas_ms; utilisation_% = tmeas_ms / tmax_ms x 100- Non-operating rows use the entered no-trip duration instead of a trip-time comparison.
- Push-button rows use the recorded function outcome rather than a timed current-injection comparison.
- The criterion is entered or selected by the user and must be checked against the project basis, current requirements and manufacturer data.
| Variable | Meaning | Unit | Use |
|---|---|---|---|
| I_dn | Rated residual current | mA | Device rating entered from the RCD, RCBO or test record. |
| m | Test multiplier | x | Selected current-injection row multiplier. |
| Itest | Test current | mA | Rated residual current multiplied by the selected row multiplier. |
| tmax_ms | Maximum trip time | ms | Selected or manually entered maximum time for a timed row. |
| tmeas_ms | Measured trip time | ms | Trip time recorded by the test instrument for a timed row. |
| tnon_s | No-trip duration | s | Entered duration for a non-operating-current row. |
| margin_ms | Time margin | ms | Difference between the entered maximum time and measured trip time. |
| utilisation_% | Time utilisation | % | Measured trip time as a share of the entered maximum time. |
| outcome | Observed outcome | - | Recorded trip, no-trip, operated or did-not-operate outcome. |
More
RCD test checker technical guide
Compare a measured RCD or RCBO test row with the entered criterion and expected outcome.
Use this page after an RCD, RCBO or safety switch test has already been taken and one line of the record needs a disciplined check. The practical problem is not usually the multiplication. The problem is whether the row says enough for another competent person to see what was tested, which criterion was used and what still needs follow-up.
The calculator compares one row at a time. That is deliberate. RCD records become weak when a half-current no-trip check, a timed current-injection check and a push-button function check are collapsed into a single note such as "RCD OK". A useful row identifies the device, the test row, the selected or manually entered criterion, the observed outcome and the measured time where a timed row applies. This page turns those values into a consistent worksheet result without claiming that the device, circuit or installation has been fully verified.
The safest way to use the page is to treat the output as a record-checking aid beside the original instrument result, switchboard schedule, asset register or commissioning sheet. It helps expose missing values and marginal timing, but it does not decide the legal test interval, installation compliance, product suitability or final defect action.
Field use cases
Use the checker when the result already exists and the next job is to make the record usable. It suits electricians checking a test sheet before it leaves site, contractors preparing a handover set, estimators pricing a maintenance allowance, supervisors checking apprentice records and facility teams comparing current and previous register rows.
| Work setting | Practical question | Useful output |
|---|---|---|
| Switchboard handover | Can this timed row be read consistently by the next electrician or reviewer? | Device reference, row, criterion, measured time, margin and status. |
| Temporary board register | Did the non-operating-current row stay closed for the recorded duration? | Test current, no-trip duration and unexpected-trip warning where relevant. |
| Facilities maintenance | Is this entry comparable with the previous register entry for the same device? | Same device label, same row wording and a clear entered basis. |
| Contractor supervision | Has a push-button function check been mixed with a timed current-injection row? | Separate function-check status from timed trip-time rows. |
| Defect follow-up | Is the concern late operation, no operation, or operation when it should not occur? | A status that points to retest, investigation or escalation. |
The calculator is not a schedule builder. It does not decide how often a workplace item must be tested, which devices must be installed, whether an installation is compliant, or whether a device should be replaced. It gives a clean reading of one row so the record can be discussed without ambiguity.
Recording one row
Start from the record in front of you, not from the result you hope to see. For a current-injection row, record the device label, rated residual current, selected row, observed trip or no-trip outcome, measured trip time where a trip is recorded, and the source of the comparison basis. For a push-button row, keep it as a function check. Do not convert it into a timed trip record.
| Record field | Strong record | Weak record |
|---|---|---|
| Device reference | Matches the board schedule, circuit list, safety switch label, asset register or test sheet. | Generic `RCD` label with no board, circuit or asset context. |
| Rated residual current | States the mA rating used for a current-injection row. | Missing rating on a 0.5x, 1x or 5x row. |
| Test row | Separates non-operating current, rated-current trip time, five-times trip time and push-button function. | Uses `tested` or `OK` without saying which row was performed. |
| Criterion basis | States Type 1, Type 2 or manual maximum where a timed row is compared. | Uses a time value without saying where the basis came from. |
| Observed outcome | Records trip, no trip, operated or did not operate. | Leaves the reader to infer the outcome from a tick or short note. |
| Measured time | Includes trip time where a timed row recorded a trip. | Says `passed` or `failed` without the measured value. |
| Source record | Keeps the instrument record, site procedure, manufacturer basis or competent-person instruction with the job pack. | Leaves the next reviewer to infer the method or threshold. |
Test row interpretation matrix
The selected row changes what a good record needs to contain. A non-operating-current row is a no-trip check for the entered duration. A rated-current row needs a time basis. A five-times row should state the entered maximum used for that row. A push-button row records the inbuilt test facility only and should not be treated as a timed current-injection result.
| Selected row | Expected record | Calculator comparison | Main follow-up if flagged |
|---|---|---|---|
| Non-operating current | Device should not trip for the entered duration. | Checks the 0.5x test current and observed no-trip outcome. | Confirm test point, loads, method and device condition if a trip is recorded. |
| Rated-current trip time | Device should trip within the entered Type 1, Type 2 or manual basis. | Compares measured time with selected or entered maximum time. | Review criterion basis, instrument record and device data if late or no trip. |
| Five-times trip time | Device should be compared with the entered maximum for the five-times row. | Uses the manual maximum time entered for the row. | Confirm the row basis before treating a fast-row result as acceptable. |
| Push-button function | Inbuilt test facility should operate. | Checks function outcome only. | Treat a failure as a device or procedure review item, not a timed-row result. |
This separation matters in real records. If a push-button result is filed as though it were a timed current-injection test, a future reviewer may assume a measurement exists when it does not. If a non-operating row is recorded as simply "no trip" without the duration and device label, the entry is hard to compare at the next inspection.
Choosing the entered criterion
The calculator only compares against the criterion entered or selected by the user. That is intentional. It avoids hiding a legal or product requirement inside the tool. Before using a preset or manual value, identify why that value belongs to the row: current standard, workplace procedure, project specification, equipment manual, regulator guidance or a competent-person instruction.
Use a preset only when it matches the row being checked. Use the manual maximum where the record, procedure or manufacturer data calls for a different timed-row basis. For a five-times row, the calculator expects a manual maximum because this page does not supply a universal hidden threshold. For a non-operating-current row, the important entered value is the duration of the no-trip check, not a trip-time maximum.
| Situation | Better calculator setting | Check before relying on it |
|---|---|---|
| Test sheet already states a Type 1 or Type 2 timed-row basis | Select the matching preset for the rated-current trip-time row. | Confirm the device and row really match that basis. |
| Procedure gives a site-specific timed maximum | Use manual maximum. | Keep the procedure, manufacturer note or instruction with the record. |
| Five-times current-injection row | Use five-times row and manual maximum. | Confirm the entered maximum is the one intended for that row. |
| Half-current no-trip row | Use non-operating current and enter the no-trip duration. | Do not add a trip-time criterion unless the device trips unexpectedly. |
| Push-button check | Use push-button function. | Keep it separate from timed current-injection evidence. |
Record wording matrix
A row can look acceptable arithmetically and still be weak as a record. The useful output is a line another competent person can trace back to the same device, row and basis.
| Weak entry | Better worksheet wording | Why it matters |
|---|---|---|
| `RCD OK` | `DB1 RCD-1, 30 mA, rated-current row, Type 2 300 ms basis, tripped 28 ms.` | Identifies the device, row, basis and measured value. |
| `No trip` | `DB-TEMP RCD-2, 30 mA, non-operating row, 15 mA for 5 s, no trip.` | Shows the half-current row and duration instead of a bare outcome. |
| `Push button OK` | `RCD-5 push-button function operated; no timed current-injection value recorded on this row.` | Keeps function evidence separate from timed testing evidence. |
| `Failed` | `RCD-3 five-times row, manual 40 ms basis, no trip recorded; retest and device review remain open under the site procedure.` | Names the row and the open action instead of hiding the failure mode. |
Interpreting margin and utilisation
Margin and utilisation are record-review values, not a final decision about the device or installation. A positive margin says the timed value is below the entered maximum for that row. A negative margin says the measured time is above the entered maximum. A small margin still deserves attention when the basis, test point or device condition is uncertain.
Do not soften a late row because the device "still tripped". Marginal or late timing can point to a wrong criterion, transcription error, test point issue, device condition, connected load effect or method problem that needs follow-up.
| Calculator output | Practical reading | Sensible record action |
|---|---|---|
| Positive margin with clear device and criterion | The timed value is within the entered basis. | Keep the row with the original instrument record and project basis. |
| Very small positive margin | The row is close to the entered maximum. | Check data entry, instrument record, device type and whether the criterion is the intended one. |
| Negative margin | Measured time is above the entered maximum. | Do not soften the result by changing the basis. Retest or investigate under the project procedure. |
| No margin shown | The selected row is non-operating, push-button or a no-trip timed failure. | Use the status and expected outcome instead of forcing a margin value. |
Worked record examples
These examples use the same row types as the calculator body. The useful comparison is the calculator status plus the action that should remain with the job record.
| Work setting | Entered row | Calculator status | Values to keep with the record |
|---|---|---|---|
| Switchboard handover | `RCD-1`, 30 mA, rated-current row, Type 2 300 ms basis, 28 ms measured. | Within entered criterion. | 30 mA test current, 300 ms maximum, 272 ms margin, board schedule and instrument record. |
| Temporary-board register | `RCD-2`, 30 mA, non-operating row, 5 s duration, no trip. | Within entered criterion. | 15 mA test current, 5 s no-trip duration and the selected test point. |
| Maintenance review | `RCD-5`, push-button function did not operate. | Function test failed. | Device reference, function-row wording and open device/procedure review action. |
| Contractor check | `RCD-3`, 30 mA, five-times row, manual 40 ms maximum, 18 ms measured. | Within entered criterion. | 150 mA test current, 22 ms margin and the source of the manual 40 ms basis. |
If a row is flagged, do not change the row type or criterion until the status looks better. First confirm whether the original record, the test setup or the device itself needs correction.
Retest or investigate
Do not solve a flagged row by changing the inputs until the status looks better. Keep the calculator record aligned with the measurement in front of the user. If the record is wrong, correct the record or retest. If the result repeats, investigate the device, test point, circuit state, connected loads, instrument setup and applicable procedure.
| Calculator status | Record wording to use | Follow-up focus |
|---|---|---|
| Within entered criterion | Keep the row with its device reference, row type, criterion basis and original instrument record. | Confirm the basis is the intended one before carrying the row into handover or maintenance records. |
| Unexpected trip recorded | State that the non-operating-current row tripped. | Confirm test setup and investigate if the trip repeats under controlled conditions. |
| No trip recorded | State that a timed row recorded no trip. | Confirm supply condition, test connection, device condition and the applicable procedure. |
| Above entered time | State the measured time and entered maximum. | Check transcription, criterion basis, test point and manufacturer data before retesting or escalating. |
| Function test failed | State that the push-button function did not operate. | Keep it as a function-check finding and review the device or procedure. |
This distinction keeps the worksheet from becoming a substitute for professional judgement. It also helps the exported row say something useful. Repeated no trip on timed row, device and setup to be investigated is clearer than a bare status.
RCBO record boundary
For RCBOs, keep the same residual-current test-row language but make the device reference specific enough to identify the RCBO, circuit and board. The overcurrent side of the RCBO, prospective fault current, loop impedance and cable withstand are separate protection questions handled by other checks.
Using the export in a job pack
The PDF export should be treated as a working record, not the original evidence by itself. Keep the original instrument record, the board or circuit schedule, the device label and any site procedure with it. The calculator output is useful when it gives the supervisor or future maintainer a compact summary of what was entered and why the row was flagged or kept for the job file.
For a clean timed row, identify the board, device, test point and criterion basis. For a flagged row, write the action still open. Do not use the export as final verification; it compares one recorded row with the basis entered by the user.
If the RCD or RCBO row raises a wider protection concern, move to the specific calculation rather than overloading this page. Use fault-loop impedance for loop-current context, short-circuit current for prospective fault-current context, and I2t cable withstand for conductor withstand against entered fault energy.
Source basis and Australian boundary
Australian RCD and RCBO testing records sit inside a wider verification and workplace-safety context. Public Australian guidance commonly distinguishes push-button checks from other testing records, and public guidance for some contexts describes no-trip and trip-time rows such as half-current non-operating checks, rated-current checks and Type 1 or Type 2 timing examples. This calculator uses those public concepts only as worksheet context.
The controlled requirements still belong to the current standards, regulator guidance, workplace procedure, manufacturer instructions and the competent person responsible for the work. AS/NZS 3760, AS/NZS 3000 and AS/NZS 3017 are mentioned as context because they are part of the Australian testing and verification environment. This page does not reproduce controlled tables and does not claim that the preset values are universal for every device or site.
Local authority, DNSP and site requirements can also matter. They may affect the test environment, documentation required before energisation or handover, acceptable evidence for a workplace record, and escalation path for a failed result. Treat those requirements as outside the calculator and attach the relevant basis to the job record where it affects the row.
Manufacturer instructions can override a generic worksheet assumption as well. Device type, electronic RCD behaviour, test button operation, line/load connection requirements, nuisance-trip history and replacement instructions should be checked from the product documentation or a competent person before relying on the row.
Stop points
- The device reference cannot be matched to the board schedule, circuit list, asset register or test sheet.
- The row type is uncertain or the criterion basis is not known.
- The measured value is missing from a timed row that should have a measured time.
- The test point, supply condition, connected load state or instrument setup cannot be confirmed.
- A non-operating row trips, a timed row records no trip, a timed row exceeds the entered basis, or a push-button check fails.
- Manufacturer instructions, workplace procedure or local requirements specify a different basis from the value entered here.
- The calculator output is being used as a compliance certificate, replacement test record or device replacement decision.
Temporary board register
A construction-board register records a 30 mA device held closed for 5 s at the non-operating-current row.
- Device reference
- DB-RCD-01
- Rated residual current
- 30 mA
- Test row
- Non-operating current
- Criterion basis
- 5 s no-trip duration
- Observed outcome
- No trip
- No-trip duration
- 5 s
- Test current30 mA x 0.5 = 15 mA
- No-trip rowRecord expects no trip for 5 s at the non-operating-current row.
The entered row is readable as a worksheet comparison.
This is a register-quality row only if the device reference, test point and instrument record identify the same RCD.
- The register identifies the tested device and location.
- The no-trip row was intentionally selected for this record.
- The project procedure still governs record acceptance.
Switchboard handover record
A switchboard handover pack includes a Type 2 timed row with a 28 ms measured trip time.
- Device reference
- DB-RCD-04
- Rated residual current
- 30 mA
- Test row
- Rated-current trip time
- Criterion basis
- Type 2 300 ms
- Observed outcome
- Trip recorded
- Measured trip time
- 28 ms
- Test current30 mA x 1 = 30 mA
- Time comparison300 ms maximum - 28 ms measured = 272 ms margin
The entered row is readable as a worksheet comparison.
The row is suitable as a worksheet comparison when the entered 300 ms basis is the intended project record basis.
- The board schedule and device reference match.
- The 300 ms basis is entered deliberately for this row.
- The original instrument record remains with the handover file.
Maintenance review flag
A facilities maintenance record shows the push-button control did not operate the device.
- Device reference
- DB-RCD-07
- Rated residual current
- 30 mA
- Test row
- Push-button function
- Criterion basis
- Function outcome
- Observed outcome
- Did not operate
- Function checkRecorded outcome is did not operate, so the row remains a function-check item.
The record should be held for device, test setup or procedure review.
The row should be treated as an action flag for device or procedure review, not as a timed operating-current result.
- The push-button row is recorded as a function check.
- The maintenance record separates this result from any timed test.
- Device review happens outside the calculator.
Five-times trip row
A switchboard record lists a 30 mA RCD on a five-times row with an entered 40 ms maximum and an 18 ms measured time.
- Device reference
- RCD-3
- Rated residual current
- 30 mA
- Test row
- Five-times trip time
- Criterion basis
- Manual 40 ms
- Observed outcome
- Trip recorded
- Measured trip time
- 18 ms
- Test current30 mA x 5 = 150 mA
- Time comparison40 ms maximum - 18 ms measured = 22 ms margin
The entered row is readable as a worksheet comparison.
The row is useful only when the entered 40 ms basis matches the project, workplace or manufacturer record for that five-times test.
- The five-times row is deliberately selected.
- The 40 ms maximum is the entered comparison basis for this record.
- The original instrument result remains available for review.