Breaker rating comparison calculator
Compare an Australian protective-device rating with entered load current and breaking-capacity fault-duty values.
load_margin_A = Irating - Iload; load_utilisation_percent = Iload / Irating x 100; fault_margin_kA = Ibreaking - Ifault; fault_utilisation_percent = Ifault / Ibreaking x 100- Device rating, load current, fault current and breaking capacity are entered by the user.
- The load-current comparison and fault-duty comparison must be reviewed separately.
- The calculator does not read trip curves, energy let-through curves or coordination settings.
- Keep manufacturer and switchboard data with the exported record.
| Variable | Meaning | Unit | Use |
|---|---|---|---|
| Irating | Protective-device rating | A | Current rating entered from the device, schedule or reviewer record. |
| Iload | Calculated load current | A | Load current entered from the load-current or project worksheet. |
| Ibreaking | Entered breaking capacity | kA | Equipment breaking-capacity value entered by the user. |
| Ifault | Prospective fault current | kA | Fault-current value entered for the comparison point. |
| load_margin_A | Load-current margin | A | Device rating minus calculated load current. |
| fault_margin_kA | Fault-duty margin | kA | Entered breaking capacity minus prospective fault current. |
| load_utilisation_percent | Load utilisation | % | Load current divided by device rating times 100. |
| fault_utilisation_percent | Fault-duty utilisation | % | Prospective fault current divided by breaking capacity times 100. |
More
Breaker rating comparison calculator technical guide
Compare an entered protective-device rating with load current and breaking-capacity values for an Australian project record.
Field use cases
Use this page when a protective-device record already has a proposed rating, a calculated load current and a prospective fault-current value. It is useful for final-circuit records, switchboard schedule reviews, maintenance findings and estimating notes where the current and breaking-capacity comparisons need to be visible on one row.
The page does not choose a protective device. It does not read device curves or select settings. It keeps two arithmetic comparisons visible: device rating against load current, and entered breaking capacity against prospective fault current.
| Work setting | Useful input | Output to record |
|---|---|---|
| Final-circuit review | Device rating and calculated load current. | Load-current margin and utilisation. |
| Switchboard duty check | Prospective current and entered breaking capacity. | Fault-duty margin and utilisation. |
| Alteration record | Existing device row and updated load/fault values. | Which comparison changed. |
| Estimating note | Provisional device value and project current values. | A transparent review row for later device data. |
Input basis
Device reference should identify the circuit breaker, fuse, RCBO, switchboard row or protective-device schedule. The same current values are less useful when the device cannot be found later.
Load current should come from a load-current worksheet, motor calculation, maximum-demand result or project schedule. Prospective fault current should come from a short-circuit current calculation, DNSP data, study or project record. Breaking capacity should come from the equipment data that applies to the device and installation condition being reviewed.
| Input | Calculator treatment | Outside the calculator |
|---|---|---|
| Device rating | Compared with entered load current. | Whether the rating suits the cable, load, installation and device type. |
| Load current | Used for load margin and utilisation. | Source calculation and demand basis. |
| Prospective fault current | Compared with entered breaking capacity. | Calculation point, source data and network contribution. |
| Breaking capacity | Used as the user-entered duty value. | Product listing, switchboard condition and manufacturer limits. |
Review workflow
- Identify the protective device and circuit or switchboard row.
- Enter the device rating in amperes.
- Enter calculated load current from the relevant source worksheet.
- Enter prospective fault current in kiloamperes for the same point.
- Enter breaking capacity from the applicable equipment record.
- Review load-current margin and fault-duty margin separately.
- Keep the source records and reviewer basis with the export.
Do not force the row into one combined answer. A device can have load-current margin while the fault-duty comparison needs review. The reverse can also happen. The page keeps the two comparisons separate for that reason.
Worked Australian examples
A final-circuit row compares a 32 A device with 24 A load current. The load-current margin is 8 A. The same row compares 6 kA prospective fault current with 10 kA entered breaking capacity, giving a 4 kA fault-duty margin.
A switchboard note compares a 40 A device with 30 A load current, but 12 kA prospective fault current against a 10 kA entered breaking capacity. The load comparison has margin, while the fault-duty comparison shows a -2 kA margin and needs review.
A load-current review compares a 20 A device with 28 A calculated load current. The load-current margin is -8 A. Even if the breaking-capacity comparison has margin, the load-current row should remain open for project review.
Boundary with related calculators
Use the load current calculator when the missing input is load current from kW, kVA, voltage and power factor. Use the short-circuit current calculator when the missing input is prospective current. Use the I2t cable withstand calculator when conductor thermal withstand and clearing time become the next question.
| Task | Use this page? | Better route when not this page |
|---|---|---|
| Compare entered device rating with entered load current. | Yes. | Not applicable. |
| Convert kW or kVA to current. | No. | Load current calculator. |
| Estimate prospective fault current. | No. | Short-circuit current calculator. |
| Compare fault energy with conductor withstand. | No. | I2t cable withstand calculator. |
| Select a protective device. | No. | Manufacturer data and project design review. |
Australian standards boundary
Australian protective-device decisions sit inside current wiring rules, manufacturer data, switchboard ratings, installation conditions, DNSP conditions where relevant and competent-person review. This page names AS/NZS 3000 as context, but it does not reproduce device tables, curves, breaking-capacity rules or selection requirements.
The entered values are placeholders for source records, not hidden authority data. A strong export names the device, the current source, the fault-current source and the breaking-capacity source. State or territory requirements, local authority expectations, product data and project documentation can override the worksheet basis.
Stop points
- The device reference cannot be matched to the schedule or switchboard row.
- Load current and fault current are from different calculation points.
- Breaking capacity is copied without the equipment source.
- Either margin is negative or very small.
- Device curves, let-through energy, selectivity or settings are required.
- The comparison is being used as device selection rather than a review row.
Final-circuit breaker comparison
A final-circuit record compares a 32 A protective device with 24 A calculated load current and 6 kA prospective fault current against a 10 kA entered breaking capacity.
- Device reference
- MCB-DB1-4
- Device rating
- 32 A
- Load current
- 24 A
- Prospective fault current
- 6 kA
- Breaking capacity
- 10 kA
- Load margin+8 A
- Load utilisation75%
- Fault-duty margin+4 kA
- Fault-duty utilisation60%
Both entered comparisons have margin.
Both entered comparisons have positive margin, but product data, installation conditions and project review still govern the device record.
- Device rating and breaking capacity are entered by the user.
- Load current and fault current come from separate source records.
- No device curve or coordination study is embedded.
Fault-duty review
A switchboard note compares a 40 A device with 30 A load current, but the entered prospective fault current is 12 kA against a 10 kA breaking-capacity value.
- Device reference
- MCB-FAULT-REVIEW
- Device rating
- 40 A
- Load current
- 30 A
- Prospective fault current
- 12 kA
- Breaking capacity
- 10 kA
- Load margin+10 A
- Load utilisation75%
- Fault-duty margin-2 kA
- Fault-duty utilisation120%
At least one entered comparison needs review.
The load-current comparison has margin, but the fault-duty comparison needs review against the source-current basis and equipment data.
- Breaking capacity is user-entered.
- Fault-duty margin is arithmetic only.
- Switchboard and manufacturer data remain external.
Load-current review
A review row compares a 20 A protective device with 28 A calculated load current and 6 kA prospective current against a 10 kA entered breaking capacity.
- Device reference
- MCB-LOAD-REVIEW
- Device rating
- 20 A
- Load current
- 28 A
- Prospective fault current
- 6 kA
- Breaking capacity
- 10 kA
- Load margin-8 A
- Load utilisation140%
- Fault-duty margin+4 kA
- Fault-duty utilisation60%
At least one entered comparison needs review.
The fault-duty comparison has margin, but the entered load current is above the entered device rating and should remain open for review.
- Load current is user-entered.
- The page does not select a larger device.
- Cable, protection and installation review remain outside this arithmetic.