Voltage unbalance calculator

Calculate three-phase voltage unbalance from one measured voltage set for Australian power-quality records.

  • Calculator
  • Power quality
  • Australia
Choose a common record type, or select Custom for a project-specific switchboard, plant or power-quality log.
Use one set only: either line-to-line voltages or phase-to-neutral voltages from the same record.
V
Enter the nominal voltage basis for the selected measurement set. Australian low-voltage records commonly use 400 V line-to-line or 230 V phase-to-neutral.
V
Enter the measured voltage between phase A and phase B.
V
Enter the measured voltage between phase B and phase C.
V
Enter the measured voltage between phase C and phase A.
%
Enter the percentage that should trigger review for this record. This is a worksheet threshold, not a published supply limit.
Record where the threshold came from before interpreting the worksheet result.
Vavg = (V1 + V2 + V3) / 3; max_deviation = max(|V1 - Vavg|, |V2 - Vavg|, |V3 - Vavg|); unbalance_% = max_deviation / Vavg x 100
  • V1, V2 and V3 must come from one measurement set only.
  • The entered threshold is a project, equipment, DNSP/report or engineering review value, not a universal published limit.
  • Negative-sequence VUF requires suitable analyser data and is outside this calculator.
Formula variables
VariableMeaningUnitUse
V1First measured voltageVVab in line-to-line mode or Van in phase-to-neutral mode.
V2Second measured voltageVVbc in line-to-line mode or Vbn in phase-to-neutral mode.
V3Third measured voltageVVca in line-to-line mode or Vcn in phase-to-neutral mode.
VavgAverage voltageVArithmetic mean of the three comparable voltage readings.
max_deviationMaximum deviationVLargest absolute difference between an entered voltage and the average.
unbalance_%Voltage unbalance%Maximum deviation divided by average voltage.
thresholdReview threshold%User-entered review value for this record.
More

Voltage unbalance calculator technical guide

Calculate three-phase voltage unbalance from one measured voltage set for Australian power-quality records.

Field use cases

Voltage unbalance work usually begins with a record, not a blank formula. A technician may have three readings written beside a main switchboard test sheet. An electrician may be looking at a plant-room complaint where one motor starter has been running hotter than expected. An engineer may receive a power-quality report and need a quick arithmetic check before deciding whether the matter belongs with load allocation, network supply, equipment selection or further logging.

This calculator is built for that first calculation record. It takes one comparable set of three voltages and turns it into an average, a maximum deviation, a spread and an entered-threshold result. It does not decide the cause. It does not say that a DNSP must act. It does not turn a spot reading into a formal network-performance finding. Its value is that it makes the record readable enough for the next technical decision.

Field use matrix
Work settingPractical questionCalculator record
Main switchboard readingAre the three line-to-line voltages materially uneven?Average voltage, highest and lowest pair, spread and unbalance percentage.
Plant-room complaintDoes the voltage record deserve equipment or logging review?Entered-threshold status plus the measured pair driving the result.
Tenancy power-quality noteAre phase-to-neutral readings being kept separate from line-to-line readings?Mode-specific labels and a record that prevents mixed measurement sets.
Generator or temporary supply testIs one measured voltage sitting away from the other two?Voltage spread, average deviation and a threshold basis for the test record.
Inverter/export observationIs a voltage snapshot worth carrying into a proper power-quality review?A record value only; DNSP and inverter settings remain separate decisions.

The most useful reading is not the percentage alone. It is the full pattern: which voltage is highest, which is lowest, how far apart they are, and whether the threshold used for the record has a clear source. A small percentage with a vague threshold is weaker than a larger percentage with a well documented record basis.

Measurement basis

The first discipline is to keep the measurement set clean. Line-to-line mode means the three entries are Vab, Vbc and Vca. Phase-to-neutral mode means the three entries are Van, Vbn and Vcn. The calculator deliberately does not let those labels become a mixed set. A mixed set may still contain real measurements, but it is not a valid basis for this arithmetic record.

Measurement set check
ItemGood recordWeak record
Measurement setVab, Vbc and Vca from the same record, or Van, Vbn and Vcn from the same record.One line-to-line value mixed with phase-to-neutral readings.
LocationMain switchboard, distribution board, plant room, tenancy board or equipment terminal is named.Readings copied without a measurement location.
Time basisSpot reading, logged average or report value is known.Values from different times treated as one set.
Instrument basisMeter, analyser or report reference is kept with the record where available.No clue how the values were obtained.
Threshold basisProject, equipment, DNSP/report or engineering threshold is recorded.A percentage copied with no source.

Australian low-voltage work commonly uses 400 V line-to-line and 230 V phase-to-neutral context, but the fields remain editable because site records, instrument reports and project documents must control the entered values. The nominal voltage field is not used to decide the unbalance percentage. It is shown to keep the average-voltage deviation visible beside the unbalance result.

Result interpretation

The formula compares each voltage with the average of the three. The voltage with the largest absolute deviation controls the percentage. That makes the result simple to read: if one phase pair or one phase-to-neutral reading is pulling away from the other two, the number rises.

Result reading matrix
OutputMeaningPractical reading
Average voltageMean of the three entered readings.Centre value for this record only.
Maximum deviationLargest absolute gap between one reading and the average.Shows which reading drives the unbalance percentage.
Voltage spreadHighest reading minus lowest reading.Quick field view of how far apart the readings are.
Voltage unbalanceMaximum deviation divided by average voltage.Main worksheet result for this page.
Average versus nominalAverage voltage compared with the entered nominal value.Helps show whether all three readings sit high or low together.
Threshold basisUser-selected source for the review percentage.Prevents the threshold from looking like a hidden site rule.

If the result is above the entered threshold, the record needs review. That does not automatically identify the cause. Possible directions include load allocation, loose or high-resistance connections, source impedance, generator regulation, inverter export condition, transformer loading, motor starting, equipment sensitivity or network-side conditions. The right direction depends on the measurement location and the operating condition recorded with the voltages.

If the result is within the entered threshold, the record is still only a record. It may be good evidence that the three readings were not materially uneven at that moment or over that report window. It does not prove that the site has no power-quality issue, and it does not replace manufacturer requirements for motors, drives, medical equipment, lifts, controls, refrigeration or other sensitive plant.

Review path

Begin by naming the record boundary. A value from the main switchboard tells a different story from a value at a motor control centre or a tenancy distribution board. Then confirm whether the numbers are spot readings, logged averages or report values. That matters because a short measurement can miss a recurring condition, while a logged record may already represent a specified interval or event filter.

Review path
StepRecord before moving onTechnical direction
Define the locationSwitchboard, plant, tenancy, generator or equipment point.Decide who owns the next review.
Confirm the measurement setLine-to-line or phase-to-neutral, not mixed.Keep the arithmetic valid.
Confirm the time basisSpot reading, logged value or report interval.Decide whether more logging is needed.
Enter the threshold basisProject, equipment, DNSP/report or engineering instruction.Keep the result from becoming a hidden rule.
Read highest and lowestVoltage pair or phase-to-neutral label.Direct the follow-up check.
Decide the next technical pathLoad allocation, motor dip, transformer loading, equipment data or formal power-quality review.Keep C24 inside its measurement-record role.

The result often leads to a separate calculator or technical review. If the voltage issue appears during motor starting, the motor voltage dip calculator is usually closer to the event. If the concern is uneven single-phase load allocation, the phase balancing calculator is the better tool because it uses currents rather than voltages. If transformer loading or source context is part of the question, transformer current and kVA can provide the surrounding load picture.

Difference from phase balancing and motor voltage dip

Voltage unbalance, phase balancing and voltage dip can appear in the same discussion, but they are not the same calculation.

Boundary with related calculators
QuestionCorrect ownerInput basis
Are measured voltages uneven?Voltage unbalance calculatorVab/Vbc/Vca or Van/Vbn/Vcn from one record.
Are phase loads uneven across L1, L2 and L3?Phase balancing calculatorEntered or measured phase currents.
What happens during a motor start?Motor voltage dip calculatorStarting current, source impedance and supply voltage.
What is the transformer current context?Transformer current and kVA calculatorkVA, voltage, phase arrangement and transformer data.

A board can have even current allocation and still show a voltage issue. A board can also have uneven current allocation without enough information to call it voltage unbalance. Treat the calculations as related evidence, not interchangeable labels.

Worked field example

A plant-room record shows 412 V between A and B, 398 V between B and C, and 386 V between C and A. The entered threshold is 2% from equipment data. The average voltage is 398.67 V. The maximum deviation is 13.33 V because Vab sits that far above the average. The voltage spread is 26 V between Vab and Vca.

Plant-room example
ValueResult
Average voltage398.67 V
Highest readingVab at 412.0 V
Lowest readingVca at 386.0 V
Maximum deviation13.33 V
Voltage spread26.00 V
Voltage unbalance3.34%
Entered threshold2.00%

The record is above the entered threshold, so the practical outcome is a review of the measurement basis and the equipment context. A motor complaint may need manufacturer data, current measurements, temperature records, start events and possibly a logged power-quality record. A distribution-board record may need load allocation, connection condition or upstream supply review. The calculator does not choose between those causes; it gives a clean arithmetic record that keeps the investigation honest.

Stop points

  • The three voltages do not belong to the same measurement set.
  • The readings were taken from different times but treated as one record.
  • A phase-to-neutral set is being compared with line-to-line results.
  • The threshold has no stated project, equipment, DNSP/report or engineering basis.
  • The result is being used as a formal supply-quality finding without instrument and measurement review.
  • The record is being used to adjust equipment or inverter settings without manufacturer and network requirements.
  • The voltage concern is actually a motor-start dip, current imbalance, harmonic issue, loose connection or protection issue that needs a different test.

When one of those stop points appears, the calculator is still useful. It shows that the arithmetic has reached the edge of its authority. That is often the most important output on a power-quality page.

Main switchboard voltage record

A main switchboard spot record shows 400 V, 397 V and 405 V line-to-line with a 2% project review threshold.

Record reference
MSB-READING
Measurement set
Line-to-line
Nominal voltage
400 V
Vab
400 V
Vbc
397 V
Vca
405 V
Review threshold
2%Project review threshold
  1. Average voltage400.67 V
  2. Maximum deviation4.33 V from the average
  3. Voltage spread8 V between the highest and lowest reading
  4. Highest and lowestVca highest, Vbc lowest
Voltage unbalance1.08%

0.17% average-voltage deviation from the entered nominal voltage.

The worksheet is within the entered threshold, so the record can be kept with its measurement basis before any broader power-quality conclusion is made.

  • The three line-to-line readings came from the same record window.
  • The threshold is a project review value entered by the user.
  • The result is not a supply-quality or equipment suitability determination.

Plant-room voltage complaint

A plant-room record beside motor complaints shows 412 V, 398 V and 386 V line-to-line against a 2% equipment-data threshold.

Record reference
PLANT-LOG
Measurement set
Line-to-line
Nominal voltage
400 V
Vab
412 V
Vbc
398 V
Vca
386 V
Review threshold
2%Equipment data
  1. Average voltage398.67 V
  2. Maximum deviation13.33 V from the average
  3. Voltage spread26 V between the highest and lowest reading
  4. Highest and lowestVab highest, Vca lowest
Voltage unbalance3.34%

-0.33% average-voltage deviation from the entered nominal voltage.

The worksheet exceeds the entered threshold. The useful action is to confirm the measurement record, equipment requirements and whether logging or further investigation is needed.

  • The readings were taken from the same switchboard or plant record.
  • The equipment threshold is entered by the user and is not embedded as a universal rule.
  • Motor loading, current balance and harmonics remain separate checks.

Tenancy phase-to-neutral log

A tenancy power-quality log records 231 V, 229 V and 226 V phase-to-neutral with a 2% project review threshold.

Record reference
TENANCY-PQ
Measurement set
Phase-to-neutral
Nominal voltage
230 V
Van
231 V
Vbn
229 V
Vcn
226 V
Review threshold
2%Project review threshold
  1. Average voltage228.67 V
  2. Maximum deviation2.67 V from the average
  3. Voltage spread5 V between the highest and lowest reading
  4. Highest and lowestVan highest, Vcn lowest
Voltage unbalance1.17%

-0.58% average-voltage deviation from the entered nominal voltage.

The phase-to-neutral set is within the entered threshold. Keep it as a separate measurement basis and do not mix it with line-to-line readings.

  • Van, Vbn and Vcn belong to the same log or measured condition.
  • Neutral, MEN and earthing matters require separate inspection or testing.
  • A spot record does not replace formal power-quality assessment.

Questions

Is voltage unbalance the same as phase balancing?

No. Phase balancing compares load currents. This calculator compares measured voltages from one voltage record.

Can I mix Vab, Vbn and Vca readings?

No. Enter one set only: Vab/Vbc/Vca or Van/Vbn/Vcn from the same record.

Does the threshold come from the calculator?

No. The threshold is entered by the user from project, equipment, DNSP/report or engineering criteria.

Does a spot reading prove network performance?

No. Logged data, instrument class, measurement location and formal review may be required.

Why is VUF not shown?

Negative-sequence VUF needs suitable analyser or sequence-component data. This page calculates the average-deviation worksheet result only.