Motor voltage dip calculator

Estimate motor-start voltage dip from starting current and source impedance or transformer kVA and impedance data for Australian 230/400 V, 50 Hz project context.

  • Calculator
  • Motors
  • Australia
Choose a common motor reference, or select Custom for a project-specific asset or schedule label.
Use source impedance where the equivalent impedance is known. Use transformer mode for a transformer-only shortcut.
Use line-to-neutral voltage for single phase and line-to-line voltage for three phase.
V
Defaults follow Australian 230/400 V supply context; edit when project data differs.
A
Enter the starting current from the motor starting-current workflow or product data.
ohm
Enter equivalent source impedance for the point being reviewed.
%
Optional. Enter a project, equipment or supply criterion for comparison; it is not created by this calculator.
Vdip = kphase x Istart x Zsource; dip_pct = Vdip / Vnom x 100; Vretained = Vnom - Vdip; transformer mode derives Zsource from kVA and Zpct
  • Source impedance can be entered directly or derived from transformer kVA and percent impedance as a shortcut.
  • The result is a voltage-change estimate for the selected point in the system.
  • Equipment tolerance, starting method and DNSP context remain separate review inputs.
Formula variables
VariableMeaningUnitUse
kphasePhase factor-1 for single phase, sqrt(3) for three phase.
IstartStarting currentAReviewed motor starting current from product data, project record or the motor starting-current calculator.
ZsourceEquivalent source impedanceohmEntered source impedance, or transformer-derived equivalent impedance in shortcut mode.
VnomNominal voltageVSelected single-phase or three-phase nominal voltage.
VdipVoltage dipVCalculated motor-start dip at the selected point.
dip_pctVoltage dip%Voltage dip expressed as a share of nominal voltage.
VretainedRetained voltageVNominal voltage minus the estimated dip.
kVATransformer ratingkVATransformer apparent-power rating used only in shortcut mode.
ZpctTransformer impedance%Transformer impedance percent used only in shortcut mode.
More

Motor voltage dip calculator technical guide

Estimate motor-start voltage dip from starting current and source impedance or transformer kVA and impedance data for Australian 230/400 V, 50 Hz project context.

Use this page when the starting current is already known and the real question is how much the motor start will depress the supply at the point being reviewed. The value is only useful when the source basis is visible beside it. A 400 V start at 0.08 ohm has a different meaning from the same current on a weaker feeder or from a transformer-only shortcut.

The practical job here is to produce a traceable record for a motor schedule, start-dip note, switchboard discussion, generator conversation or early design review. The calculator does not judge whether the dip is acceptable. It shows the estimate and keeps the basis explicit so the next person can see what still needs checking.

Field use cases

Practical motor voltage-dip use cases
Work settingReal questionUseful action from this page
Pump or fan start noteWhat dip should be carried into an early project record when the starting current is already known?Enter the reviewed starting current, the source basis and the nominal voltage, then record the dip with the source note.
Weak feeder discussionIs the start likely to pull the voltage down enough to need a deeper look?Compare the calculated dip with an entered criterion and keep the result as a review note, not a final decision.
Transformer-led estimateWhat can be said before a full source study or full feeder model exists?Use the transformer kVA and impedance shortcut to capture the transformer contribution only.
Replacement motor recordWill the new motor start behave differently from the motor that was previously on the job?Compare the new starting current and the resulting dip against the older record before copying assumptions forward.
Site handover or maintenance noteWhat should be left behind for the next electrician or engineer?Record motor reference, current source, supply basis, criterion and the reason the value was used as a project estimate.

The source basis is the part of the result that makes the percentage usable. It tells the reviewer whether the dip came from an equivalent impedance, a transformer shortcut or a more complete project review.

Source-basis matrix

Source basis and comparison fields
Source basisWhen it is usefulWhat data overrides itWhat it does not modelNext check
Equivalent source impedanceA project, supply or calculation note provides impedance for the point being reviewed.Updated supply study, DNSP data, measured/site-derived values or engineered supply calculation.Motor torque, upstream permissions, downstream cable contribution unless already included.Confirm the point of connection and the source of the impedance.
Transformer kVA and impedanceTransformer data is available before a full supply study is available.Full supply study, transformer manufacturer data, feeder contribution or generator supplier data.Wider network strength, downstream conductors, generator response and other connected load effects.Treat as transformer contribution unless the wider source is explicitly included.
Entered criterionA project, equipment or supply criterion is available for comparison.Current project specification, DNSP condition, equipment tolerance or manufacturer instruction.Final equipment suitability by itself.Check who owns the criterion and whether it applies at the reviewed point.
Reviewed starting currentProduct data or a separate motor starting-current calculation is available.Manufacturer locked-rotor data, starter settings, drive current limit or commissioning evidence.Which starting method is correct, generator response or starter suitability.Check the current source before adjusting the source basis.

The same motor can be described with different levels of certainty. Source impedance is the strongest basis when it is tied to the point being reviewed. Transformer kVA and impedance is useful when that is all the project has, but it should not be presented as the whole supply network unless the wider source contribution is already included.

Review workflow

  1. Confirm the motor reference used on the drawing, schedule, asset register or maintenance note.
  2. Confirm the starting-current source. If the value came from the motor starting-current workflow, keep that basis visible.
  3. Choose the supply arrangement and nominal voltage. Use 230 V for single phase and 400 V for three phase unless the project data says otherwise.
  4. Choose the source basis that matches the information available. Use equivalent source impedance where a point-of-connection value exists. Use transformer kVA and %Z only as a transformer shortcut.
  5. Enter a criterion only when there is a real project, equipment or supply value to compare against.
  6. Read the retained voltage and the margin together. If the margin is negative, or if the retained voltage is physically implausible, stop and recheck the inputs and the source basis before relying on the record.
  7. Export the result only after the source basis, current source and criterion source are visible in the note or record pack.

This workflow keeps the page in the right place. It estimates the start event and records the basis for later review; it is not a final equipment decision sheet.

How to read the result

Voltage-dip result interpretation
Result stateWhat it meansPractical response
No criterion enteredThe page has produced a voltage-dip estimate only.Use the value for early discussion, then add a documented project, equipment or supply criterion before relying on it.
Within entered criterionThe calculated dip is not above the comparison value entered by the user.Check that the criterion applies to the reviewed point and keep the source basis with the exported record.
Above entered criterionThe calculated dip exceeds the comparison value entered by the user.Recheck starting current, source impedance, equipment tolerance and project requirements before carrying the value forward.
Negative criterion marginThe calculated dip is higher than the entered criterion by the displayed margin.Treat this as a review trigger, not a standalone failure statement.
Retained voltage is implausibleThe entered current, voltage or source basis creates a retained voltage that does not make physical sense.Stop and correct the inputs or supply calculation before using the result.
Transformer shortcut usedThe calculation is based on transformer rating and impedance only.Add feeder, upstream supply or generator data if the decision depends on the full source path.

The state is a comparison aid, not a final declaration. A low calculated dip can still be the wrong project answer if the source basis is weak, the current came from the wrong starting method, or equipment tolerance has not been checked.

Worked scenarios

Example motor-start records
SituationInputsResultFollow-up supported
DOL pump at a strong supply point400 V three phase, 91.2 A starting current, 0.08 ohm source impedance, 10% criterion12.64 V dip, 3.16% dip, 387.36 V retained, 6.84% marginEarly project note where starting current and source impedance already have a documented basis.
Soft starter on a weaker feeder400 V three phase, 126 A starting current, 0.18 ohm source impedance, 8% criterion39.28 V dip, 9.82% dip, 360.72 V retained, -1.82% marginReview of current limit, source data and equipment tolerance before downstream use.
Transformer-only preliminary record400 V three phase, 126 A starting current, 100 kVA transformer, 5% impedance, 8% criterion17.46 V dip, 4.36% dip, 382.54 V retained, transformer full-load current 144.34 ATransformer contribution estimate before feeder or wider source data is available.
Small single-phase maintenance note230 V single phase, 22 A starting current, 0.2 ohm source impedance, no criterion entered4.40 V dip, 1.91% dip, 225.60 V retained, estimate onlyMaintenance record where no project criterion has been documented.

These examples show the difference between a numerical answer and a usable engineering note. The 3.16% result on the pump is a traceable estimate, not a final decision. The 9.82% case is a prompt to check the current source, feeder strength and equipment data that govern the next decision.

Boundary lines

Where this calculator stops and other tools take over
Related taskUse this page?Why
Motor full-load currentNoUse the motor full-load current calculator to establish running current first.
Motor starting currentNoUse the motor starting-current calculator when the start current still needs to be estimated.
Running cable voltage dropNoUse the cable voltage-drop calculator for steady-state running load, not the start event.
Generator starting kVANoGenerator sizing needs its own load-sequence and manufacturer review.
Final project decisionNoThis page is a record tool; final decision still depends on current requirements, equipment data and project review.

The boundary is deliberate. Motor full-load current gives running current. Motor starting current gives starting current. This worksheet turns starting current into a voltage-dip estimate. When the question changes to generator capability, final protection settings or final project decision, the voltage-dip record should stop being the main tool.

Australian context

Australian motor-start work is usually read against 230/400 V a.c., 50 Hz project context, but the actual site story still comes from the local authority, DNSP conditions, equipment data and current Australian standards. A calculator like this is helpful because it keeps the start event visible in a format that can be carried into a job pack, a design note or a handover record.

That said, the current being used, the source impedance being entered and the transformer data being assumed must still come from somewhere real. If the site has a weak supply, a long feeder, a soft starter, a drive, a high-inertia load or a sensitive adjacent installation, the start dip is only one part of the conversation. The numbers here can guide that conversation, but they do not replace manufacturer instructions or project-specific electrical judgement.

Stop points

  • The starting current source is not known or cannot be matched to the motor reference.
  • The source impedance value is being copied without a documented basis.
  • The transformer shortcut is being used as if it described the whole supply network.
  • The entered criterion is being treated as a final threshold rather than a comparison value.
  • The retained voltage looks physically implausible for the selected data.
  • The real question is generator selection, final equipment decision, motor torque behaviour or running voltage drop rather than motor-start dip.

When one of those points appears, stop treating the calculator as the answer and return to the source data, equipment data or wider project review.

DOL pump source-impedance check

A contractor carries a 91.2 A starting-current estimate into a start-dip note using an entered 0.08 ohm equivalent source impedance.

Motor reference
PMP-2
Calculation basis
Source impedance
Supply arrangement
Three phase
Nominal voltage
400 V
Starting current
91.2 A
Source impedance
0.08 ohm
Entered criterion
10%
  1. Equivalent source impedance0.08 ohm
  2. Voltage dip12.64 V
  3. Voltage dip percentage3.16%
  4. Retained voltage387.36 V
  5. Criterion margin6.84%
Estimated voltage dip3.16%

Use the value with the stated source basis and project review.

The dip is below the entered criterion, but the record still needs the source of the impedance value before it is used in a project decision.

  • 400 V line-to-line three-phase supply context.
  • Starting current is already estimated or reviewed.
  • 0.08 ohm is treated as equivalent source impedance for the calculation point.

Soft-starter source review

A reviewer checks a 126 A soft-starter current against a weaker source impedance and an entered voltage-dip criterion.

Motor reference
MTR-9
Calculation basis
Source impedance
Supply arrangement
Three phase
Nominal voltage
400 V
Starting current
126 A
Source impedance
0.18 ohm
Entered criterion
8%
  1. Equivalent source impedance0.18 ohm
  2. Voltage dip39.28 V
  3. Voltage dip percentage9.82%
  4. Retained voltage360.72 V
  5. Criterion margin-1.82%
Estimated voltage dip9.82%

The estimate is above the entered criterion.

The estimate is above the entered criterion. The next action is to check current limit, source data and equipment tolerance before relying on the value.

  • 400 V line-to-line three-phase supply context.
  • Starting current comes from the motor starting-current workflow or product data.
  • Entered criterion is a user input, not a final decision limit created by this page.

Transformer shortcut record

A preliminary record uses transformer rating and impedance percent where a full source impedance is not yet available.

Motor reference
MTR-T1
Calculation basis
Transformer kVA and %Z
Supply arrangement
Three phase
Nominal voltage
400 V
Starting current
126 A
Transformer rating
100 kVA
Transformer impedance
5%
Entered criterion
8%
  1. Equivalent source impedance0.08 ohm
  2. Voltage dip17.46 V
  3. Voltage dip percentage4.36%
  4. Retained voltage382.54 V
  5. Criterion margin3.64%
Estimated voltage dip4.36%

Use the value with the stated source basis and project review.

The transformer shortcut gives a reproducible transformer-contribution estimate only. It does not include downstream cable or other supply contribution unless those are included separately.

  • 100 kVA transformer rating is entered by the user.
  • 5% transformer impedance is entered from project or manufacturer data.
  • The shortcut does not replace a wider supply review.

Questions

When should I use the transformer shortcut?

Use it only when transformer kVA and impedance percent are the best source values you have. It is a shortcut for the transformer contribution, not a full supply study.

Does this replace a voltage-drop calculation?

No. Running voltage drop and motor-start voltage dip answer different questions. Use the cable voltage-drop calculator for running load and this page for the start event.

Can I treat a small dip as acceptable?

Not from this page alone. Use project criteria, equipment data, DNSP conditions and the actual supply context before deciding whether the estimate is acceptable.

What should I record with the result?

Record the starting-current source, source impedance or transformer basis, nominal voltage, motor reference, any entered criterion and the reason the estimate is being used.

Does this calculate motor starting current?

No. Starting current comes from the motor starting-current workflow, product data or a reviewed estimate. This page only turns that current into a voltage-dip estimate.