Lighting circuit load calculator
Calculate Australian lighting load and group current from luminaire quantity, watts per fitting, allowance, phase arrangement and entered review current.
Pconnected_W = N x Wfit; Padjusted_W = Pconnected_W x (1 + allowance_pct / 100); Pgroup_W = Padjusted_W / G; Igroup = Pgroup_W / (F x V x PF)- The allowance is a user-entered project factor for drivers, control gear or spare capacity.
- Group current assumes the adjusted load is divided evenly across the entered groups.
- Lighting design, emergency lighting, product data and circuit protection remain separate checks.
| Variable | Meaning | Unit | Use |
|---|---|---|---|
| N | Luminaire quantity | fittings | Number of fittings in the lighting row. |
| Wfit | Watts per fitting | W | Electrical load per luminaire from product data or the luminaire schedule. |
| allowance_pct | Allowance | % | Driver, ballast, control gear or project allowance entered by the user. |
| Pconnected_W | Connected lighting load | W | Quantity multiplied by watts per fitting. |
| Padjusted_W | Adjusted lighting load | W | Connected load after the entered allowance is applied. |
| G | Groups | groups | Number of equal lighting circuit groups or rows. |
| Pgroup_W | Load per group | W | Adjusted load divided by the entered groups. |
| F | Phase factor | factor | Use 1 for single phase and square root of 3 for balanced three phase. |
| V | Nominal AC voltage | V | 230 V single-phase or 400 V three-phase basis by default. |
| PF | Power factor | ratio | Entered driver or project value used for current conversion. |
| Igroup | Current per group | A | Primary current estimate for the entered lighting group. |
| Ireview | Review current | A | Optional user-entered current for comparison. |
More
Lighting circuit load calculator technical guide
Calculate lighting load and group current from luminaire quantity, watts per fitting, allowance, phase arrangement and entered review current.
Use this page when a lighting row needs to become a traceable electrical load before it is entered into a circuit schedule, estimate, switchboard worksheet or maximum-demand review. The calculator is deliberately narrow: it adds fitting watts, applies an entered allowance, divides the row into equal groups and estimates current from the entered voltage and power factor.
The useful record is not "lighting allowed for". A stronger record says, for example, "LTG-1, 12 fittings at 18 W, 10% allowance, 230 V, PF 0.90, one group, 1.15 A per group". That row can then be checked against the circuit schedule, grouping plan, voltage-drop review, controls arrangement and product data.
Field use cases
| Work setting | Real question | Useful action from this page |
|---|---|---|
| Residential or small commercial circuit | What current follows from the selected fittings? | Enter quantity, watts per fitting, allowance and single-phase voltage to create a circuit row. |
| Corridor or tenancy lighting row | Should a repeated lighting row be split across several groups? | Enter the full row and group count so the per-group current is visible. |
| Car park or external lighting group | What is the balanced three-phase current for the entered lighting load? | Select three phase only when the row is being treated as a balanced three-phase group. |
| Estimate or variation review | Did a luminaire-count change materially affect the lighting load? | Compare connected load, adjusted load and current per group before updating the estimate. |
| Switchboard or maximum-demand worksheet | What lighting current should be carried forward? | Export the row with allowance, power factor and grouping basis attached. |
This page is most useful before the lighting row is copied into another document. Once a vague value is buried in a schedule, it becomes hard to tell whether the number came from product data, an allowance, a rounded estimate or a design change.
Lighting load data checklist
| Value | Where it normally comes from | Why it matters |
|---|---|---|
| Schedule reference | Lighting schedule, drawing, circuit schedule or quote line | Keeps the calculated row traceable. |
| Luminaire quantity | Luminaire schedule, marked-up drawing or takeoff | Sets the connected load before allowances. |
| Watts per fitting | Product data, luminaire schedule or supplier document | Drives the load calculation directly. |
| Allowance | Driver data, control gear basis, project requirement or estimator decision | Prevents the row from hiding the difference between product watts and planning watts. |
| Groups | Circuit schedule, area split, tenancy split or load-row decision | Divides the total row into the current carried by each group. |
| Voltage and phase basis | Project electrical basis | Single-phase and balanced three-phase current calculations use different denominators. |
| Power factor | Driver data or project basis | Converts lighting watts into estimated current. |
| Review current | User-entered project comparison value | Gives a visible comparison without publishing a hidden circuit-rating rule. |
If the luminaire schedule is provisional, keep the calculator record provisional as well. Changing from a nominated luminaire to another driver, wattage or power factor can change the current even when the physical fitting count stays the same.
Circuit grouping matrix
| Grouping basis | What the calculator does | Practical check |
|---|---|---|
| One group | Carries the full adjusted lighting load into one current result. | Check whether the row represents one circuit, one area or a single schedule line. |
| Several equal groups | Divides the adjusted load by the entered group count. | Confirm the fittings are actually split in a way that makes equal grouping reasonable. |
| Balanced three-phase group | Uses the three-phase current relationship for the entered row. | Use only when the lighting row is intended to be treated as balanced three-phase load. |
| Area-based split | Can be represented by a group count if each group is similar. | Use separate rows where areas, luminaire types or switching arrangements differ materially. |
| Mixed fittings | Should usually be separated into rows. | Do not average unlike fittings if product watts or power factor differs enough to matter. |
Grouping is a record decision, not a design approval. A group current can look acceptable while the actual installation still needs switching, emergency lighting, cable route, voltage-drop, protection and controls review.
Review current matrix
| Result state | What it means | Practical action |
|---|---|---|
| Within entered review current | The calculated group current is not above the user-entered comparison value. | Carry the row forward with the luminaire, allowance and grouping basis visible. |
| Above entered review current | The calculated group current exceeds the entered comparison value. | Review grouping, luminaire data, allowance, voltage basis and downstream circuit design. |
| No review current | The calculator reports the current estimate only. | Use the output as a load row, not as a circuit-capacity statement. |
| Very low utilisation | The row may be lightly loaded against the entered value. | Confirm the row has not been over-grouped or copied with the wrong fitting count. |
| Very high allowance | The arithmetic may be correct but the basis needs explanation. | Keep the allowance source with the exported record. |
The review current is not supplied by this page. It is an entered project comparison value. This keeps the calculator transparent and avoids turning a simplified worksheet into a circuit-design rule.
Review workflow
- Identify the lighting row or area from the drawing, luminaire schedule, takeoff or quote.
- Confirm whether the row should be single phase or a balanced three-phase group.
- Enter the luminaire quantity and watts per fitting from the current product or schedule basis.
- Enter any driver, ballast, control gear or project allowance used for the load row.
- Enter the number of equal circuit groups represented by the row.
- Confirm the voltage and power factor used for current conversion.
- Enter a review current only when the project has a comparison value to use.
- Read connected load, adjusted load and current per group together.
- Carry the row into maximum demand, voltage drop, circuit schedule or estimating work as required.
- Stop before treating the result as lux design, cable sizing, protection selection or compliance approval.
This sequence keeps the lighting load calculation in its proper role. The row is a current estimate and record aid. It is not a substitute for the decisions that come after the row is known.
Worked records
| Situation | Inputs | Result | Example record row |
|---|---|---|---|
| Small LED circuit | 12 fittings, 18 W each, 10% allowance, 230 V, PF 0.90, one group | Adjusted load 237.6 W, current 1.15 A | "LTG-1 carried forward as one single-phase lighting group." |
| Corridor row split across groups | 45 fittings, 24 W each, 10% allowance, three groups, PF 0.95 | Adjusted load 1188.0 W, group current 1.81 A | "CORRIDOR-LTG split across three equal lighting groups for schedule review." |
| Car park balanced three-phase group | 72 fittings, 38 W each, 10% allowance, 400 V, PF 0.95 | Adjusted load 3009.6 W, group current 4.57 A | "CARPARK-LTG treated as balanced three-phase lighting load for worksheet purposes." |
These examples show why the record should not be reduced to a watts-to-amps conversion. Quantity, allowance, phase basis and grouping can each change the current that is carried into the next document.
Using the result in actual work
The result usually leaves the calculator as one row in a larger document. In an estimate, the connected load can support a variation note when luminaire counts change. In a circuit schedule, the group current helps the reviewer see whether rows have been split as intended. In a maximum-demand worksheet, the adjusted lighting row should sit beside other loads without pretending to be the whole installation result.
| Result pattern | What it usually means | Practical follow-up |
|---|---|---|
| Low group current | The row is light against the entered review value. | Check the luminaire count and grouping before assuming the row is harmless. |
| Current near the entered value | The row may be sensitive to wattage, allowance or grouping changes. | Recheck product watts and driver data before exporting the record. |
| Current above the entered value | The row needs a circuit or grouping review. | Split the row, review the comparison value or move into detailed design. |
| Multiple luminaire types | The row may hide unlike loads. | Create separate rows where product watts or power factor differs. |
| Provisional product data | The row may change after procurement. | Mark the export as based on the current luminaire schedule or supplier information. |
Good lighting load records make later checking easier. They show the load basis before someone starts debating cable size, voltage drop, switching zones or maximum demand.
Boundary with neighbouring calculations
| Related task | Use this page? | Why |
|---|---|---|
| General watts-to-current conversion | Sometimes | Use this page only when luminaire count, allowance and grouping matter. Use load current for ordinary loads. |
| Whole-installation maximum demand | No | Maximum demand belongs in the maximum-demand calculator or a project load schedule. |
| Cable voltage drop | No | Voltage drop needs cable length, conductor data and installation assumptions. |
| Cable sizing or protection | No | Cable size and protective-device selection require installation conditions and standards review. |
| Lux, lumens or lighting layout | No | Lighting design depends on room geometry, photometry, task requirements, reflectance, mounting and product data. |
| Emergency lighting | No | Emergency lighting design and verification are separate from this load arithmetic. |
Keeping this boundary clear protects the value of the page. The calculator gives a transparent lighting load and current row. It does not pretend to design the lighting installation.
Australian context
Australian lighting load planning normally sits inside a 230/400 V, 50 Hz installation context, but the final use of the result depends on the project. Current Australian standards, local authority requirements, project specifications, product data, controls requirements and manufacturer instructions can govern the final design.
This page does not reproduce controlled standards content and does not publish fixed circuit ratings. It records arithmetic from the values entered by the user so the lighting row can be reviewed in the proper electrical documents.
Stop points
- The luminaire count is not confirmed from a luminaire schedule, drawing or takeoff.
- The watts per fitting are taken from a marketing description rather than electrical product data.
- The allowance is copied without a project or manufacturer basis.
- Mixed fitting types are averaged into one row without review.
- A balanced three-phase basis is selected for a row that is not actually balanced.
- The result is used for cable sizing, protective-device selection or voltage drop without the relevant downstream checks.
- The result is treated as lighting design, lux compliance or emergency-lighting verification.
- Current standards, project specifications, local authority requirements or manufacturer instructions are being treated as optional.
Small LED lighting circuit
A small lighting circuit has 12 LED fittings at 18 W each, with a 10% project allowance and a 10 A entered review current.
- Supply arrangement
- Single phase
- Luminaire quantity
- 12
- Watts per fitting
- 18 W
- Allowance
- 10%
- Groups
- 1
- Connected load216 W
- Adjusted load237.6 W
Carry this as a lighting group current, subject to the project basis.
The group current is low against the entered review current, but the row still needs circuit design, switching, cable and product-data review.
- 230 V single-phase lighting group context.
- Power factor and allowance are project inputs.
- The entered review current is not a hidden circuit-rating rule.
Corridor lighting split across three groups
A corridor row has 45 fittings at 24 W each, divided evenly across three lighting groups with a 10% allowance.
- Supply arrangement
- Single phase
- Luminaire quantity
- 45
- Watts per fitting
- 24 W
- Allowance
- 10%
- Groups
- 3
- Connected load1080 W
- Adjusted load1188 W
Carry this as a lighting group current, subject to the project basis.
The total row load is distributed across the entered groups. The grouping basis should stay with the schedule.
- Equal grouping is assumed for the worksheet.
- Fitting watts and power factor come from the project basis.
- Cable sizing and voltage drop remain separate checks.
Balanced three-phase car park lighting group
A car park lighting group has 72 fittings at 38 W each, with a 10% allowance and a balanced three-phase supply basis.
- Supply arrangement
- Three phase
- Luminaire quantity
- 72
- Watts per fitting
- 38 W
- Allowance
- 10%
- Groups
- 1
- Connected load2736 W
- Adjusted load3009.6 W
Carry this as a lighting group current, subject to the project basis.
The result is a balanced three-phase current estimate for the entered group, not a lighting-layout or compliance decision.
- 400 V line-to-line balanced three-phase context.
- The row is treated as a balanced lighting group.
- Lighting controls, emergency lighting and product compliance sit outside this calculator.